F7V2 Sound transmission through walls [F7P2(a)]
Part F7 Sound transmission and insulation · NCC 2019: FV5.2
Compliance with F7P2(a) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS/NZS ISO 717.1; or
a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45 when determined under AS/NZS ISO 717.1; or
any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25 when determined under AS/NZS ISO 717.1.
Changed in NCC 2025 (minor wording). See NCC 2025 Volume One F7V2, or show what changed.
Compliance with F7P2(a) to avoid the transmission of airborne sound … (DnT,w + Ctr) not less than 45 when determined under AS/NZS AS ISO 717.1; or a wall separating a sole-occupancy unit from … level difference (DnT,w) not less than 45 when determined under AS/NZS AS ISO 717.1; or any door assembly located in a wall … level difference (DnT,w) not less than 25 when determined under AS/NZS AS ISO 717.1.
Removed words are struck through; added words are highlighted. Comparison of the text only.