F7V4 Sound transmission through walls [F7P4(1)(a) and (2)]
Part F7 Sound transmission and insulation · NCC 2019: FV5.4
Compliance with F7P4(1)(a) and (2) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
a wall separating sole-occupancy units has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS ISO 717.1; or
a wall separating a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS ISO 717.1.
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One F7V4, or show what changed.
Compliance with F7P4(1)(a) and (2) to avoid the transmission of … level difference (DnT,w) not less than 40 when determined under AS/NZS AS ISO 717.1; or a wall separating a sole-occupancy unit from … level difference (DnT,w) not less than 40 when determined under AS/NZS AS ISO 717.1.
Removed words are struck through; added words are highlighted. Comparison of the text only.