F7V4 Sound transmission through walls [F7P4(1)(a) and (2)]
Part F7 Sound transmission and insulation · NCC 2019: FV5.4
Compliance with F7P4(1)(a) and (2) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
a wall separating sole-occupancy units has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1; or
a wall separating a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1.
Changed in NCC 2025 (minor wording). See NCC 2025 Volume One F7V4, or show what changed.
Compliance with F7P4(1)(a) and (2) to avoid the transmission of … level difference (DnT,w) not less than 40 when determined under AS/NZS AS ISO 717.1; or a wall separating a sole-occupancy unit from … level difference (DnT,w) not less than 40 when determined under AS/NZS AS ISO 717.1.
Removed words are struck through; added words are highlighted. Comparison of the text only.