Deemed-to-Satisfy Provision · NCC 2025 Volume One
G5D3 Protection — residential buildings
Part G5 Construction in bushfire prone areas · NCC 2019: NSW G5.2, G5.2
Varied in NSW. Check the variation for your state.
In a designated bushfire prone area the following must comply with AS 3959:
A Class 2 or 3 building.
A Class 10a building or deck immediately adjacent or connected to a Class 2 or 3 building.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One G5D3.
Can't meet G5D3? A Performance Solution must meet the Performance Requirements it satisfies: G5P1, G5P2. Start a Performance Solution →