Deemed-to-Satisfy Provision · NCC 2025 Volume One

G5D2 Application of Part

Part G5 Construction in bushfire prone areas · NCC 2019: G5.1, NSW G5.1, QLD G5.1

Open G5D2 on NCC Online ↗
Varied in NSW, QLD. Check the variation for your state.

The Deemed-to-Satisfy Provisions of this Part apply in a designated bushfire prone area to—

a Class 2 or 3 building; or

a building located in an area subject to a Bushfire Attack Level (BAL) not exceeding BAL—12.5, determined in accordance with AS 3959 that is—

a Class 9a health-care building; or

a Class 9b—

early childhood centre; or

primary or secondary school; or

a Class 9c residential care building; or

a Class 10a building or deck immediately adjacent or connected to a—

Class 2 or 3 building; or

a building of a type listed in (b).

Notes

If a building of a type listed in (b) or (c)(ii) is subject to a BAL exceeding BAL—12.5, the building would need to comply with Performance Requirement G5P2 by means of a Performance Solution. There are no Deemed-to-Satisfy Provisions for these buildings.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One G5D2.