G5D2 Application of Part
Part G5 Construction in bushfire prone areas · NCC 2019: G5.1, NSW G5.1, QLD G5.1
The Deemed-to-Satisfy Provisions of this Part apply in a designated bushfire prone area to—
a Class 2 or 3 building; or
a building located in an area subject to a Bushfire Attack Level (BAL) not exceeding BAL—12.5, determined in accordance with AS 3959 that is—
a Class 9a health-care building; or
a Class 9b—
early childhood centre; or
primary or secondary school; or
a Class 9c residential care building; or
a Class 10a building or deck immediately adjacent or connected to a—
Class 2 or 3 building; or
a building of a type listed in (b).
Notes
If a building of a type listed in (b) or (c)(ii) is subject to a BAL exceeding BAL—12.5, the building would need to comply with Performance Requirement G5P2 by means of a Performance Solution. There are no Deemed-to-Satisfy Provisions for these buildings.
State and territory variations all clauses side by side →
- NSW Replaced Delete clause G5D2 and insert NSW G5D2 as follows: The Deemed-to-Satisfy Provisions of this Part apply in a designated bushfire…
- QLD Replaced Delete clause G5D2 and insert QLD G5D2 as follows: (1) The Deemed-to-Satisfy Provisions of this Part apply in a designated…