Deemed-to-Satisfy Provision · NCC 2025 Volume One
G5D4 Protection — certain Class 9 buildings
Part G5 Construction in bushfire prone areas
Varied in NSW. Check the variation for your state.
(1) In a designated bushfire prone area the following must comply with Specification 43:
A Class 9a health-care building.
A Class 9b—
early childhood centre; or
primary or secondary school.
A Class 9c residential care building.
(2) In a designated bushfire prone area, a Class 10a building or deck immediately adjacent or connected to a building of a type listed in (1) must comply with S43C2 and S43C13.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One G5D4.
Can't meet G5D4? A Performance Solution must meet the Performance Requirements it satisfies: G5P1, G5P2. Start a Performance Solution →