Deemed-to-Satisfy Provision · NCC 2025 Volume One

I3D11 Portable fire extinguishers

Part I3 Farm buildings and farm sheds · NCC 2019: H3.11

Open I3D11 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) A farm building not provided with a fire hose reel system in accordance with E1D3 must be provided with—

one portable fire extinguisher rated at not less than 5ABE in each room containing flammable materials or electrical equipment; and

one portable fire extinguisher rated at not less than 4A60BE adjacent to every required exit door; and

location signs complying with clauses 3.3 to 3.9 of AS 2444 above each required portable fire extinguisher.

(2) A farm shed must be provided with not less than one portable fire extinguisher for every 500 m2 of floor area or part thereof, distributed as evenly as practicable throughout the building.

(3) A portable fire extinguisher required by (2) must be—

of ABE type; and

not less than 4.5 kg in size; and

installed in accordance with Section 3 of AS 2444.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One I3D11.

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used