South Australia variation · NCC 2025 Volume One

SA I3D11 Portable fire extinguishers

SA Part I3 Farm buildings and farm sheds · varies I3D11 Portable fire extinguishers

Open on NCC Online ↗

Delete clause I3D11 and insert SA I3D11 as follows:

(1) For Class A fire risks in a farm building the requirements of E1D14 need not be provided if—

portable fire extinguishers for Class A fire risks are provided in accordance with SA I3D11(2); or

notwithstanding the exemption provided by SA I3D10, a fire hose reel system is provided in accordance with E1D3, or wash-down hoses or similar hoses that are—

not more than 36 m long; and

equipped with a spray nozzle suitable for fighting a fire at the incipient stage; and

permanently connected to a water supply which is sufficient to supply two hoses discharging at the rate of 20 litres per minute for 60 minutes; and

arranged to provide coverage to all points on the floor within.

(2) Portable fire extinguishers provided to comply with SA I3D11(1)(a) must be—

located at or adjacent to every required exit; or

in open walled farm buildings, one extinguisher is provided for every 500 m2 of floor area, or part thereof.

New in NCC 2025. No SA I3D11 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause