New South Wales variation · NCC 2025 Volume One

NSW C3D6 Class 9 buildings

NSW Part C3 Compartmentation and separation · varies C3D6 Class 9 buildings

Open on NCC Online ↗

Delete subclause C3D6(3) and insert NSW C3D6(3) as follows:

(3) A Class 9c building must comply with the following:

A building must be divided into areas not more than 500 m2 by smoke proof walls complying with Specification 11.

A fire compartment must be separated from the remainder of the building by fire walls and notwithstanding C3D8 and Specification 5, floors with an FRL of not less than 60/60/60.

Except for walls provided in accordance with (3)(a) and (b), non-loadbearing internal walls, and if a building is of Type C construction — all internal walls, between and bounding sole-occupancy units and bounding a public corridor in a resident use area must:

be lined on each side with standard grade plasterboard not less than 13 mm thick or a material with at least an equivalent level of fire protection; and

if provided with cavity insulation, contain only non-combustible insulation; and

extend to the underside of—

the floor next above; or

a ceiling lined with standard grade plasterboard not less than 13 mm thick or an equivalent non-combustible material; or

a non-combustible roof covering; and

not incorporate any penetrations above door head height unless the penetrations are adequately stopped to prevent the free passage of smoke; and

be smoke sealed with intumescent putty or other suitable material at any construction joint, space or the like between the top of the wall and the floor, ceiling or roof.

Load bearing internal walls must comply with the requirements of Specification 5 and (c)(ii), (iii), (iv) and (v) above.

Ancillary use areas containing equipment or materials that are a high potential fire hazard, must be separated from the sole-occupancy units by smoke proof walls complying with Specification 11.

The ancillary use areas referred to in (e) include, but are not limited to, the following:

A kitchen and related food preparation areas having a combined floor area of more than 30 m2.

A laundry, where items of equipment are of the type that are potential fire sources (e.g. gas fire dryers).

Storage rooms greater than 10 m2 used predominantly for the storage of administrative records.

Openings in fire walls must be protected as follows:

Doorways — self-closing or automatic closing –/60/30 fire doors.

Windows — automatic or permanently fixed closed –/60/– fire windows or –/60/– automatic fire shutters.

Other openings — construction having an FRL not less than –/60/–.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One NSW C3D6.