Deemed-to-Satisfy Provision · NCC 2025 Volume One

C3D6 Class 9 buildings

Part C3 Compartmentation and separation · NCC 2019: C2.5

Open C3D6 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) A Class 9a health-care building must comply with the following:

patient care areas must be divided into fire compartments not exceeding 2000 m2.

A fire compartment must be separated from the remainder of the building by fire walls and—

in Type A construction—floors and roof or ceiling as required in Specification 5; and

in Type B construction—floors with an FRL of not less than 120/120/120 and with the openings in external walls bounding patient care areas being vertically separated in accordance with the requirements of C3D7 as if the building were of Type A construction.

Ward areas —

where the floor area exceeds 1000 m2, must be divided into floor areas not more than 1000 m2 by walls with an FRL of not less than 60/60/60; and

where the floor area exceeds 500 m2, must be divided into floor areas not more than 500 m2 by smoke-proof walls complying with Specification 11; and

where the floor area is not more than 500 m2, must be separated from the remainder of the patient care area by smoke-proof walls complying with Specification 11; and

where division of ward areas by fire-resisting walls under (a) or (c)(i) is not required, any smoke-proof wall required under (c)(ii) or (iii) must have an FRL of not less than 60/60/60.

Treatment areas —

where the floor area exceeds 1000 m2, must be divided into floor areas not more than 1000 m2 by smoke-proof walls complying with Specification 11; and

where the floor area is not more than 1000 m2, must be separated from the remainder of the patient care area by smoke-proof walls complying with Specification 11.

Ancillary use areas located within a patient care area and containing equipment or materials that are a high potential fire hazard, must be separated from the remainder of the patient care area by walls with an FRL of not less than 60/60/60.

The ancillary use areas referred to in (e) include, but are not limited to, the following:

A kitchen and related food preparation areas having a combined floor area of more than 30 m2.

A room containing a hyperbaric facility (pressure chamber).

A room used predominantly for the storage of medical records having a floor area of more than 10 m2.

A laundry, where items of equipment are of the type that are potential fire sources (e.g. gas fire dryers).

A wall required by (e) to separate ancillary use areas from the remainder of the building must extend to the underside of—

the floor above; or

a non-combustible roof covering; or

a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes.

Openings in walls required by (c) and (e) to have an FRL must be protected as follows:

Doorways—self-closing or automatic closing –/60/30 fire doors.

Windows—automatic or permanently fixed closed –/60/– fire windows or –/60/– automatic fire shutters.

Other openings—construction having an FRL not less than –/60/–.

(2) In a building containing a Class 9b early childhood centre —

unless the Class 9b early childhood centre is the only use in the building, it must be separated from the remainder of the building by walls and/or floors with an FRL not less than that required for a fire wall; and

each storey within the Class 9b early childhood centre must contain not less than 2 fire compartments.

(3) A Class 9c building must comply with the following:

A building must be divided into areas not more than 500 m2 by smoke-proof walls complying with Specification 11.

A fire compartment must be separated from the remainder of the building by fire walls and, notwithstanding C3D8 and Specification 5, floors with an FRL of not less than 60/60/60.

Internal walls (other than those bounding lift and stair shafts) supported by floors provided in accordance with (b) need not comply with Specification 5 if they have an FRL not less than 60/–/–.

Ancillary use areas containing equipment or materials that are a high potential fire hazard, must be separated from the sole-occupancy units by smoke-proof walls complying with Specification 11.

The ancillary use areas referred to in (d) include, but are not limited to, the following:

A kitchen and related food preparation areas having a combined floor area of more than 30 m2.

A laundry, where items of equipment are of the type that are potential fire sources (e.g. gas fired dryers).

Storage rooms greater than 10 m2 used predominantly for the storage of administrative records.

Openings in fire walls must be protected as follows:

Doorways —self-closing or automatic closing –/60/30 fire doors.

Windows —automatic or permanently fixed closed –/60/– fire windows or –/60/– automatic fire shutters.

Other openings — construction having an FRL not less than –/60/–.

Exemptions

C3D6(2) does not apply to a Class 9b early childhood centre —

wholly within a storey that provides direct egress to a road or open space; or

with a rise in storeys of not more than 2, where the Class 9b early childhood centre is the only use in the building.

New in NCC 2025. No C3D6 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet C3D6? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →