New South Wales variation · NCC 2025 Volume One

NSW C4D12 Bounding construction: Class 2 and 3 buildings and Class 4 parts

NSW Part C4 Protection of openings · varies C4D12 Bounding construction: Class 2 and 3 buildings and Class 4 parts

Open on NCC Online ↗

Delete subclause C4D12(4) and insert NSW C4D12(4) as follows:

(4) Except as provided for in NSW C4D12(5), protection for a doorway required under (1), (2) or (3) must be at least—

in a building of Type A construction — a self-closing –/60/30 fire door; and

in a building of Type B or C construction — a self-closing, tight fitting, solid core door not less than 35 mm thick.

Delete subclause C4D12(5) and insert NSW C4D12(5) as follows:

(5) In a Class 3 building used as a residential care building protected with a sprinkler system complying with Specification 17, protection for a doorway must be at least a tight fitting solid core door not less than 35 mm thick that is—

self-closing; or

fitted with a free-arm action closing device which closes the door or causes the door to remain closed (without preventing manual re-opening), upon the detection of smoke caused by a smoke detector located within the room.

Insert NSW subclause C4D12(10) in clause C4D12 as follows:

(10) In a Class 9b building used as an entertainment venue, openings in construction required to separate one space from another must be protected in accordance with C4D5.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One NSW C4D12.