New South Wales variation · NCC 2025 Volume One

NSW D3D16 Thresholds

NSW Part D3 Construction of exits · varies D3D16 Thresholds

Open on NCC Online ↗

Delete clause D3D16 and insert NSW D3D16 as follows:

The threshold of a doorway must not incorporate a step or ramp at any point closer to the doorway than the width of the door leaf unless the doorway opens to an external space; and—

where the doorway serves an area required to be accessible by Part D4, it is provided with a threshold ramp or step ramp in accordance with AS 1428.1; or

where (a) does not apply—

in a Class 9b building used as an entertainment venue, the door sill is not more than 50 mm above the finished surface of the ground, balcony, or the like to which the door opens; or

except as provided by (i), the door sill is not located below, and is not more than 190 mm above the finished surface of the ground, balcony, or the like to which the doorway opens.

Exemptions

NSW D3D16 does not apply to a plant room, machinery room, or the like.

Changed since NCC 2022. See NCC 2022 Volume One NSW D3D16, or show what changed.

Delete clause D3D16 and insert NSW D3D16 as follows: The … the doorway than the width of the door leaf unless — in patient care areas in a Class 9a health-care building, the door sill is not more than 25 mm above the finished floor level to which the doorway opens; or in resident use areas in a Class 9c building, a ramp is provided with a maximum gradient of 1:8 for a maximum height of 25 mm over opens to an external space; and — where the threshold; or in a building doorway serves an area required to be accessible by Part D4, the doorway — opens to a road or open space; and it is provided with a threshold ramp or step ramp in accordance with AS 1428.1; or where (a) does not apply — in a Class 9b building used as an entertainment venue, the door sill of a doorway opening to a road, open space, external stair landing or external balcony is not more than 50 mm above the finished floor level surface of the ground, balcony, or the like to which the doorway door opens; or in other cases — the doorway opens to a road or open space, external stair landing or external balcony; and except as provided by (i), the door sill is not located below, and is not more than 190 mm above the finished surface of the ground, balcony, or the like, like to which the doorway opens. Exemptions NSW D3D16 does not apply to a plant room, machinery room, or the like.