New South Wales variation · NCC 2025 Volume One

NSW G5D4 Protection – Class 9 buildings used as a special fire protection purpose

NSW Part G5 Construction in bushfire prone areas · varies G5D4 Protection — certain Class 9 buildings

Open on NCC Online ↗

Delete clause G5D4 and insert NSW G5D4 as follows:

In a designated bushfire prone area, a Class 9 building that is a special fire protection purpose or a Class 10a building or deck immediately adjacent or connected to a such a building or part, must comply with—

for a Class 9 building that is special fire protection purpose, Specification 43 except as amended by Planning for Bush Fire Protection; or

for a Class 10a building or deck immediately adjacent or connected to a Class 9 building that is a special fire protection purpose —

AS 3959 except as amended by Planning for Bush Fire Protection; and

S43C13; or

the requirements of (a) or (b) above as modified by the development consent or a bushfire safety authority issued under section 100B of the Rural Fires Act 1997.

Changed since NCC 2022. See NCC 2022 Volume One NSW G5D4, or show what changed.

Delete clause G5D4 and insert NSW G5D4 as follows: In … (a) or (b) above as modified by the development consent with or a bushfire safety authority issued under section 100B of the Rural Fires Act 1997 for the purposes of integrated development. 1997.

Removed words are struck through; added words are highlighted. Comparison of the text only.