NSW I4D4 Sprinkler systems for common foyers
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
Delete clause I4D4 and insert NSW I4D4 as follows:
In an entertainment venue, where multiple auditoriums have a foyer in common, the following applies:
If the foyer serves not more than 2 auditoriums, that foyer must be separated from any adjoining foyer by construction having an FRL of not less than 60/60/60.
If the foyer serves more than 2 auditoriums, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 must be installed—
throughout the storey containing the foyer; and
throughout each storey in the building below that storey.
Changed since NCC 2022. See NCC 2022 Volume One NSW I4D4, or show what changed.
Delete clause I4D4 and insert NSW I4D4 as follows: In an entertainment venue, where multiple auditoriums have a foyer … and throughout each storey in the building below that storey.
Removed words are struck through; added words are highlighted. Comparison of the text only.