New South Wales variation · NCC 2025 Volume One
NSW I4D9 Conventional stages: fire separation of stages
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
Delete clause I4D9 and insert NSW I4D9 as follows:
A stage which is more than 50 m2 in area, and all areas below such a stage, must (with the exception of the proscenium opening) be separated from the backstage and the remainder of the building by construction having an FRL of not less than 60/60/60.
Changed since NCC 2022. See NCC 2022 Volume One NSW I4D9, or show what changed.