New South Wales variation · NCC 2025 Volume One

NSW J1V4 Verification of building envelope sealing

NSW Part J1 Energy efficiency performance requirements · varies J1V4 Verification of building envelope sealing

Open on NCC Online ↗

Insert NSW clause J1V4 in clause J1V4 as follows:

Compliance with NSW J1P1(a) is verified for building envelope sealing when the envelope is sealed at an air permeability rate, tested in accordance with Method 1 of AS/NZS ISO 9972, of not more than—

for a Class 5, 6, 8 or 9a or 9b building, other than a ward area, in climate zones 1, 7 and 8, 5 m³/hr.m² at 50 Pa reference pressure; or

for a Class 3 or 9c building, or a Class 9a ward area in climate zones 1, 3, 4, 6, 7 and 8, 5 m³/hr.m² at 50 Pa reference pressure.

Changed since NCC 2022. See NCC 2022 Volume One NSW J1V4, or show what changed.

(1) Insert NSW clause J1V4 in clause J1V4 as follows: Compliance with NSW J1P1(e) and NSW J1P6 J1P1(a) is verified for building envelope sealing when the envelope is … 1 of AS/NZS ISO 9972, of not more than — for a Class 2 building or a Class 4 part of a building, 10 m³/hr.m² at 50 Pa reference pressure; or for a Class 5, 6, 8 or 9a or 9b … 7 and 8, 5 m³/hr.m² at 50 Pa reference pressure. (2) In a sole-occupancy unit of a Class 2 building or a Class 4 part of a building, where an air permeability rate of not more than 5 m3/hr.m2 at 50 Pa reference pressure is achieved — a mechanical ventilation system must be provided that — can be manually overridden; and provides outdoor air, either — continuously; or intermittently, where the system has controls that enable operation for not less than 25 per cent of each 4 hour segment; and provides a flow rate not less than that achieved with the following formula: [formula] , where — [formula] = the required air flow rate (L/s); and [formula] = the total area of the sole-occupancy unit of a Class 2 or Class 4 part of a building (m2); and [formula] = the number of bedrooms in the sole-occupancy unit of a Class 2 or Class 4 part of a building; and [formula] = the fraction of time within each 4 hour segment that the system is operational; and any space with a solid-fuel burning combustion appliance must be ventilated with permanent openings directly to outside with a free area of not less than half of the cross-sectional area of the appliance’s flue; and any space with a gas-fueled combustion appliance must be ventilated in accordance with — clause 6.4 of AS/NZS 5601.1; and clause 6.4.5 of AS/NZS 5601.1. (3) For the purposes of (2)(c), the volume of the space is considered to be 1 m3 for determining ventilation requirements.

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause