New South Wales variation · NCC 2025 Volume One

NSW J5D2 Application of Part

NSW Part J5 Building sealing · varies J5D2 Application of Part

Open on NCC Online ↗

Delete clause J5D2 and insert NSW J5D2 as follows:

The Deemed-to-Satisfy Provisions of this Part apply to elements forming the envelope of a Class 3 and Class 5 to 9 building, other than—

a building in climate zones 1, 2, 3 and 5 where the only means of air-conditioning is by using an evaporative cooler; or

a permanent building opening, in a space where a gas appliance is located, that is necessary for the safe operation of a gas appliance; or

a building or space where the mechanical ventilation required by Part F6 provides sufficient pressurisation to prevent infiltration; or

parts of buildings that cannot be fully enclosed.

Changed since NCC 2022. See NCC 2022 Volume One NSW J5D2, or show what changed.

Delete clause J5D2 and insert NSW J5D2 as follows: The Deemed-to-Satisfy Provisions of this Part apply to elements forming the envelope of a Class 2 3 and Class 5 to 9 building, other than — a building in climate … necessary for the safe operation of a gas appliance; or in a Class 3 or Class 5 to 9 building, a building or space where the mechanical ventilation required by … infiltration; or parts of buildings that cannot be fully enclosed.

Removed words are struck through; added words are highlighted. Comparison of the text only.