New South Wales variation · NCC 2025 Volume One
NSW J6D4 Mechanical ventilation system control
NSW Part J6 Air-conditioning and ventilation · varies J6D4 Mechanical ventilation system control
Delete subclause J6D4(1) and insert NSW J6D4(1) as follows:
(1) A mechanical ventilation system, including one that is part of an air-conditioning system, must be capable of being deactivated when the building or part of the building served by that system is not occupied.
Delete subclause J6D4(6) and insert NSW J6D4(6) as follows:
(6) The requirements of (2), (4) and (5) do not apply to a mechanical ventilation system that serves only one sole-occupancy unit in a Class 3 or 9c building.
New in NCC 2025. No NSW J6D4 in NCC 2022 Volume One; it may have moved or been renumbered.