Northern Territory variation · NCC 2025 Volume One

NT F7D6 Walls between a bathroom, sanitary compartment, laundry or kitchen and a habitable room in adjoining unit

NT Part F7 Sound transmission and insulation · varies F7D6 Sound insulation rating of walls

Open on NCC Online ↗

Insert NT clause F7D6 in clause F7D6 as follows:

(1) Except for a Class 9c building, a wall separating a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining unit must—

have an RW of not less than 50; and

provide satisfactory insulation against impact sound; and

not incorporate a duct which reduces the RW of the wall to less than 50.

(2) A wall satisfies (1)(a) and (b) if it is—

in accordance with (3); or

for other than masonry, in 2 or more separate leaves without rigid mechanical connection except at their periphery; or

identical to a prototype that is no less resistant to the transmission of impact sound when tested in accordance with NT Specification 29 than a wall listed in (3).

(3) For the purposes of (2)(a) and (c), the construction of walls to reduce the transmission of impact sound must be as follows:

Cavity brickwork: two leaves of 90 mm brick masonry with—

all joints filled solid with mortar; and

an air space not less than 40 mm between the leaves; and

the leaves connected only by ties in accordance with AS 3700.

Single leaf brickwork: 110 mm thick brick masonry with—

each face rendered 13 mm thick; and

50 mm x 12 mm thick timber battens at not more than 610 mm centres fixed to each face but not recessed into the render; and

one layer of 12 mm thick softboard nailed to the battens; and

6 mm thick medium density hardboard adhesive-fixed to the softboard.

Concrete blockwork: 190 mm thick concrete block masonry with—

each face of the blocks fitted with 50 mm x 50 mm timber battens, spaced at not more than 610 mm centres, screw-fixed into resilient plugs with rubber inserts; and

the space between the battens completely filled with mineral or glass wool blanket or batts not less than 50 mm thick; and

the outer face of the battens finished with plasterboard not less than 10 mm thick or other material with a mass per unit area not less than 7.3 kg/m2.

Changed since NCC 2022. See NCC 2022 Volume One NT F7D6, or show what changed.

Insert NT clause F7D6 in clause F7D6 as follows: (1) Except for a Class 9c building, a wall separating … a mass per unit area not less than 7.3 kg/m2.

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause