NT F7D6 Walls between a bathroom, sanitary compartment, laundry or kitchen and a habitable room in adjoining unit
NT Part F7 Sound transmission and insulation · varies F7D6 Sound insulation rating of walls
(1) Except for a Class 9c building, a wall separating a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining unit must—
have an RW of not less than 50; and
provide satisfactory insulation against impact sound; and
not incorporate a duct which reduces the RW of the wall to less than 50.
(2) A wall satisfies (1)(a) and (b) if it is—
in accordance with (3); or
for other than masonry, in 2 or more separate leaves without rigid mechanical connection except at their periphery; or
identical to a prototype that is no less resistant to the transmission of impact sound when tested in accordance with NT Specification 29 than a wall listed in (3).
(3) For the purposes of (2)(a) and (c), the construction of walls to reduce the transmission of impact sound must be as follows:
Cavity brickwork: two leaves of 90 mm brick masonry with—
all joints filled solid with mortar; and
an air space not less than 40 mm between the leaves; and
the leaves connected only by ties in accordance with AS 3700.
Single leaf brickwork: 110 mm thick brick masonry with—
each face rendered 13 mm thick; and
50 mm x 12 mm thick timber battens at not more than 610 mm centres fixed to each face but not recessed into the render; and
one layer of 12 mm thick softboard nailed to the battens; and
6 mm thick medium density hardboard adhesive-fixed to the softboard.
Concrete blockwork: 190 mm thick concrete block masonry with—
each face of the blocks fitted with 50 mm x 50 mm timber battens, spaced at not more than 610 mm centres, screw-fixed into resilient plugs with rubber inserts; and
the space between the battens completely filled with mineral or glass wool blanket or batts not less than 50 mm thick; and
the outer face of the battens finished with plasterboard not less than 10 mm thick or other material with a mass per unit area not less than 7.3 kg/m2.
Changed in NCC 2025. See NCC 2025 Volume One NT F7D6, or show what changed.
Insert NT clause F7D6 in clause F7D6 as follows: (1) Except for a Class 9c building, a wall separating … a mass per unit area not less than 7.3 kg/m2.
Removed words are struck through; added words are highlighted. Comparison of the text only.