NT F7D7 Soil and waste pipes to be separated
NT Part F7 Sound transmission and insulation · varies F7D7 Sound insulation rating of internal services
Insert NT clause F7D7 in clause F7D7 as follows:
If a soil or waste pipe, including a pipe that is embedded in or passes through a floor, serves or passes through more than one sole-occupancy unit —
the pipe must be separated from the rooms of any sole-occupancy unit by construction with an RW not less than—
45 if the adjacent room is a habitable room (other than a kitchen); or
30 if the adjacent room is a kitchen or any other room; and
a door or panel provided access to the pipe must not open into any habitable room (other than a kitchen); and
an access door or panel in any other part must be firmly fixed so as to overlap the frame or rebate of the frame by not less than 10 mm, be fitted with a sealing gasket along all edges and be constructed of—
wood, particleboard or blockboard not less than 38 mm thick; or
compressed fibre reinforced cement sheeting not less than 9 mm thick; or
other suitable material with a mass per unit area not less than 24.4 kg/m2.
Changed since NCC 2022. See NCC 2022 Volume One NT F7D7, or show what changed.
Insert NT clause F7D7 in clause F7D7 as follows: If a soil or waste pipe, including a pipe that … a mass per unit area not less than 24.4 kg/m2.
Removed words are struck through; added words are highlighted. Comparison of the text only.