Deemed-to-Satisfy Provision · NCC 2025 Volume One
F7D7 Sound insulation rating of internal services
Part F7 Sound transmission and insulation · NCC 2019: NT F5.6, F5.6
Varied in NT. Check the variation for your state.
(1) If a duct or soil, waste or water supply pipe, including a duct or pipe that is located in a wall or floor cavity, serves or passes through more than one sole-occupancy unit, the duct or pipe must be separated from the rooms of any sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than—
40 if the adjacent room is a habitable room (other than a kitchen); or
25 if the adjacent room is a kitchen or non-habitable room.
(2) If a stormwater pipe passes through a sole-occupancy unit, it must be separated in accordance with (1)(a) and (b).
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F7D7.
Can't meet F7D7? A Performance Solution must meet the Performance Requirements it satisfies: F7P1, F7P2, F7P3, F7P4. Start a Performance Solution →