Fire-protective covering
Any one or more of the following:
13 mm fire-protective grade plasterboard.
12 mm cellulose cement flat sheeting complying with AS/NZS 2908.2 or ISO 8336.
12 mm fibrous plaster reinforced with 13 mm x 13 mm x 0.7 mm galvanised steel wire mesh located not more than 6 mm from the exposed face.
Other material not less fire-protective than 13 mm fire-protective grade plasterboard, fixed in accordance with the normal trade practice for a fire-protective covering.
Used in
- S10C2 General requirements
- S10C3 Massive timber
- S11C3 Class 9c buildings
- S5C21 Type B fire-resisting construction — fire-resistance of building elements
- S5C23 Type B fire-resisting construction — Class 2 and 3 buildings: Concession
- S5C24 Type C fire-resisting construction — fire-resistance of building elements
- C2D11 Fire hazard properties
- C3D10 Separation of classifications in different storeys
- C4D12 Bounding construction: Class 2 and 3 buildings and Class 4 parts
- C4D13 Openings in floors and ceilings for services
- D3D8 Installations in exits and paths of travel
- D3D30 Timber stairways: Concession