Specification clause · NCC 2025 Volume One

S10C4 Form of test

Specification 10 Fire-protected timber · NCC 2019: Spec C1.13a: 3.1

Open S10C4 on NCC Online ↗

(1) Tests must be carried out in accordance with the Standard Fire Test, or an equivalent or more severe test, on the timber element with the proposed non-combustible coverings fixed in a representative manner, with the time the timber interface temperatures exceeded 300°C confirmed in a report from an Accredited Testing Laboratory.

(2) If a fire protection system incorporates joints, the test specimens must incorporate representative joints.

(3) Interface temperatures must be measured over the following features by a minimum of two thermocouples:

At joint positions in the protection systems.

At least 200 mm from any joint.

At service penetrations.

At any other locations where, in the opinion of the Accredited Testing Laboratory, the interface temperature may be higher than the above positions.

(4) The temperatures must be measured in accordance with Appendix C1 and Section 2 of AS 1530.4 as appropriate.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S10C4.