S10C3 Massive timber
Specification 10 Fire-protected timber · NCC 2019: Spec C1.13a: 2.2
(1) Fire-protected timber, where the timber is massive timber, need not comply with S10C2 if the fire-protected timber —
utilises a non-combustible fire-protective covering fixed in accordance with system requirements to achieve an FRL not less than that required for the building element; and
has a non-combustible fire-protective covering fixed in accordance with system requirements—
so as the temperature at the interface between the protection system and the timber does not exceed 300°C during a fire resistance test performed in accordance with S10C4, S10C5 and S10C6 for the application and periods listed in Table S10C3; or
not less than that specified by Table S10C3; and
has any cavity filled with non-combustible insulation, or no cavity, between—
the surface of the timber and the fire-protective covering; or
timber elements within the fire-protective covering.
(2) For the purposes of (1), the non-combustible fire-protective covering provided under (1)(b) may form all or part of the non-combustible fire-protective covering provided under (1)(a).
Table S10C3 Interface temperature and minimum fire protective grade plasterboard thickness
Application
Time – without timber interface exceeding 300°C (mins)
Minimum thickness of fire-grade plasterboard (mm)
Inside a fire-isolated stairway or lift shaft
20
13
External walls within 1 m of an allotment boundary or 2 m of a building on the same allotment
45
2 x 13
All other applications
30
16
Tables
Clauses referred to
- S10C2 General requirements
- S10C4 Form of test
- S10C5 Smaller specimen permitted
- S10C6 Acceptance criteria