Specification clause · NCC 2025 Volume One

S11C4 Doorways in smoke-proof walls

Specification 11 Smoke-proof walls in health-care and residential care buildings · NCC 2019: Spec C2.5: 4

Open S11C4 on NCC Online ↗

A door required by C3D6 or this Specification to be smoke-proof or have an FRL must provide a smoke reservoir by not extending within 400 mm of the underside of—

a roof covering; or

the floor above; or

an imperforate false ceiling that will prevent the free passage of smoke.

Changed since NCC 2022. See NCC 2022 Volume One S11C4, or show what changed.

A door required by C3D6 or this Specification to be smoke-proof or have an FRL, other than one that serves a fire compartment provided with a zone pressurisation system in accordance with AS 1668.1, FRL must provide a smoke reservoir by not extending within 400 … false ceiling that will prevent the free passage of smoke.

Removed words are struck through; added words are highlighted. Comparison of the text only.