Specification 11 Smoke-proof walls in health-care and residential care buildings · NCC 2019: Spec C2.5: 4
A door required by C3D6 or this Specification to be smoke-proof or have an FRL, other than one that serves a fire compartment provided with a zone pressurisation system in accordance with AS 1668.1, must provide a smoke reservoir by not extending within 400 mm of the underside of—
a roof covering; or
the floor above; or
an imperforate false ceiling that will prevent the free passage of smoke.
Changed in NCC 2025. See NCC 2025 Volume One S11C4, or show what changed.
A door required by C3D6 or this Specification to be smoke-proof or have an FRL, other than one that serves a fire compartment provided with a zone pressurisation system in accordance with AS 1668.1, FRL must provide a smoke reservoir by not extending within 400 … false ceiling that will prevent the free passage of smoke.