S21C3 Smoke exhaust fans

Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 3

Open S21C3 on NCC Online ↗

Each smoke exhaust fan, complete with its drive, flexible connections, control gear and wiring must—

be constructed and installed so that it is capable of continuous operation (exhausting the required volumetric flow rate at the installed system resistance) at a temperature of 200°C for a period of not less than 1 hour; and

in a building not fitted with a sprinkler system, be capable of continuous operation at a temperature of 300°C for a period of not less than 30 minutes; and

be rated to handle the required volumetric flow rate at ambient temperature to be capable of exhausting cool smoke during the early stages of a fire and to allow routine testing; and

have any high temperature overload devices installed, automatically overridden during the smoke exhaust operation.

New in NCC 2025. No S21C3 in NCC 2022 Volume One; it may have moved or been renumbered.