Specification clause · NCC 2025 Volume One

S21C2 Smoke exhaust capacity

Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 2

Open S21C2 on NCC Online ↗

(1) Smoke exhaust fans must have a sufficient capacity to contain the smoke layer—

within a smoke reservoir formed in accordance with S21C4 and not less than 2 m above the highest floor level; and

above the top of any openings interconnecting different smoke reservoirs.

(2) Exhaust rates must be determined in accordance with Figure S21C2, with the height measurement taken from the lowest floor level to the underside of the smoke layer and the fire load determined in accordance with Table S21C2.

Table S21C2 Fire load (MW)

Classification

Fire load (MW) for unsprinklered buildings

Fire load (MW) for sprinklered buildings

Class 2, 3 or 5

5

1.5

Class 6

10

5

Class 7 or 8

15

5

Class 9 — generally

5

1.5

Class 9b buildings covered by Part I1 (see Note) or exhibition halls

10

5

Table Notes

If the smoke reservoir above the stage is smoke separated from the audience area, the fire load specified applies to the stage area only and the fire load for the audience area is as per Class 9 generally.

Figure S21C2 Smoke exhaust rate

Tables

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S21C2.