S21C2 Smoke exhaust capacity
Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 2
(1) Smoke exhaust fans must have a sufficient capacity to contain the smoke layer—
within a smoke reservoir formed in accordance with S21C4 and not less than 2 m above the highest floor level; and
above the top of any openings interconnecting different smoke reservoirs.
(2) Exhaust rates must be determined in accordance with Figure S21C2, with the height measurement taken from the lowest floor level to the underside of the smoke layer and the fire load determined in accordance with Table S21C2.
Table S21C2 Fire load (MW)
Classification
Fire load (MW) for unsprinklered buildings
Fire load (MW) for sprinklered buildings
Class 2, 3 or 5
5
1.5
Class 6
10
5
Class 7 or 8
15
5
Class 9 — generally
5
1.5
Class 9b buildings covered by Part I1 (see Note) or exhibition halls
10
5
Table Notes
If the smoke reservoir above the stage is smoke separated from the audience area, the fire load specified applies to the stage area only and the fire load for the audience area is as per Class 9 generally.
Figure S21C2 Smoke exhaust rate