NCC 2025 Volume One
Specification 21 Smoke exhaust systems
9 clauses · Open on NCC Online ↗
- S21C1 ScopeThis Specification describes the requirements for mechanical smoke exhaust systems.
- Table S21C2 Fire load (MW)Classification | Fire load (MW) for unsprinklered buildings | Fire load (MW) for sprinklered buildings Class 2, 3 or 5 | 5 | 1.5 Class 6 | 10 | 5…
- S21C2 Smoke exhaust capacitySmoke exhaust fans must have a sufficient capacity to contain the smoke layer— within a smoke reservoir formed in accordance with S21C4 and not less…
- S21C3 Smoke exhaust fansEach smoke exhaust fan, complete with its drive, flexible connections, control gear and wiring must— be constructed and installed so that it is…
- S21C4 Smoke reservoirsA fire compartment must be divided at ceiling level into smoke reservoirs formed by smoke baffles/curtains of non-combustible and non-shatterable…
- S21C5 Smoke exhaust fan and vent locationSmoke exhaust fans and vents must be located— such that each smoke reservoir is served by one or more fans with the maximum exhaust rate at any one…
- S21C6 Make-up airLow level make-up air must be provided either automatically or via permanent ventilation openings to replace the air exhausted so as to minimise—…
- S21C7 Smoke exhaust system controlEach smoke exhaust fan must be activated sequentially by smoke detectors complying with Specification 20 and arranged in zones to match the smoke…
- S21C8 Smoke detectionA smoke detection system must be installed in accordance with Specification 20 to activate the smoke exhaust system.