Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 5
Smoke exhaust fans and vents must be located—
such that each smoke reservoir is served by one or more fans with the maximum exhaust rate at any one point limited to avoid extracting air from below the smoke layer; and
to prevent the formation of stagnant regions resulting in excessive cooling and downward mixing of smoke; and
at natural collection points for the hot smoky gases within each smoke reservoir having due regard to the ceiling geometry and its effect on the migratory path of the smoke; and
away from the intersection of walkways or malls; and
to ensure that any voids containing escalators and/or stairs commonly used by the public are not used as a smoke exhaust path; and
to discharge directly to outdoor with a velocity of not less than 5 m/s, at a suitable point not less than 6 m from any air intake point or exit.