S21C6 Make-up air

Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 6

Open S21C6 on NCC Online ↗

(1) Low level make-up air must be provided either automatically or via permanent ventilation openings to replace the air exhausted so as to minimise—

any disturbance of the smoke layer due to turbulence created by the incoming air; and

the risk of smoke migration to areas remote from the fire due to the effect of make-up air on the air balance of the total system.

(2) The velocity of make-up air through doorways must not exceed 2.5 m/s.

(3) Within a multi-storey fire compartment, make-up air must be provided across each vertical opening from a building void to the fire-affected storey at an average velocity of 1 m/s so as to minimise the spread of smoke from the fire-affected storey to other storeys.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S21C6.