Specification clause · NCC 2025 Volume One

S23C5 Smoke alarms

Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 2(c)

Open S23C5 on NCC Online ↗

(1) Extra-low voltage smoke alarms must be compatible with the local fire indicator panel.

(2) Low voltage smoke alarms must be configured to send an output alarm signal to the local fire indicator panel.

(3) Unless there is internal isolation of the signal output conductors, they must at all times be treated as low voltage conductors.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S23C5.