Specification clause · NCC 2025 Volume One
S23C6 Signal isolation interface units
Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 2(d)
(1) Signal isolation interface units must isolate any low voltage connected to the smoke alarms from the local fire indicator panel.
(2) Signal isolation interface units must be certified by an Accredited Testing Laboratory as compatible with the specific types of smoke alarms used in the system.
(3) Signal isolation interface units must be accepted by the electricity supply authority.
(4) Units must be marked in a clearly visible location, with letters greater than or equal to 35 mm containing the following information:
SMOKE ALARM SIGNAL ISOLATION UNIT WARNING – 240 V
Isolate power supply before removing cover
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S23C6.