S31C8 Operation of atrium mechanical air-handling systems

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.2

Open S31C8 on NCC Online ↗

Mechanical air-handling systems serving an atrium must be designed to operate so that during a fire—

a tenable atmosphere is maintained in all paths of travel along balconies to required exits during the period of evacuation; and

smoke exhaust fans serving the atrium are only activated when smoke enters the atrium; and

central plant systems do not use the atrium as a return air path; and

central plant systems which use return air paths remote from the atrium —

cycle to the full outside air mode; and

stop supply air to the fire affected storey or fire compartment; and

continue to fully exhaust the fire affected storey or fire compartment and reduce the exhaust from other storeys or fire compartments by at least 75%; and

continue to supply air to fire compartments or storeys other than the fire affected storey or fire compartment; and

fans performing relief or exhaust duty from the atrium stop normal operation; and

floor by floor, or unitary, air-handling plant serving a single fire compartment or storey —

ceases normal operation in the fire affected storey or fire compartment; and

commences full relief or exhaust from that fire affected storey or fire compartment; and

continue to supply air to fire compartments or storeys other than the fire affected storey or fire compartment.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S31C8.