S31C8 Operation of atrium mechanical air-handling systems
Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.2
Mechanical air-handling systems serving an atrium must be designed to operate so that during a fire—
a tenable atmosphere is maintained in all paths of travel along balconies to required exits during the period of evacuation; and
smoke exhaust fans serving the atrium are only activated when smoke enters the atrium; and
central plant systems do not use the atrium as a return air path; and
central plant systems which use return air paths remote from the atrium—
cycle to the full outside air mode; and
stop supply air to the fire affected storey or fire compartment; and
continue to fully exhaust the fire affected storey or fire compartment and reduce the exhaust from other storeys or fire compartments by at least 75%; and
continue to supply air to fire compartments or storeys other than the fire affected storey or fire compartment; and
fans performing relief or exhaust duty from the atrium stop normal operation; and
floor by floor, or unitary, air-handling plant serving a single fire compartment or storey—
ceases normal operation in the fire affected storey or fire compartment; and
commences full relief or exhaust from that fire affected storey or fire compartment; and
continue to supply air to fire compartments or storeys other than the fire affected storey or fire compartment.