Specification clause · NCC 2025 Volume One

S31C9 Activation of smoke control system

Specification 31 Fire and smoke control systems in buildings containing atriums · NCC 2019: Spec G3.8: 3.3

Open S31C9 on NCC Online ↗

(1) The smoke control system must be activated by—

operation of an automatic fire alarm; or

operation of the sprinkler system; or

a manual start switch.

(2) All controls for the smoke control system must be located—

in the fire control room; or

in the emergency control centre (if any); or

adjacent to the sprinkler control valves; or

incorporated in the Fire Indicator Panel.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S31C9.