Specification clause · NCC 2025 Volume One

S32C6 Proscenium curtains

Specification 32 Construction of proscenium walls · NCC 2019: Spec H1.3: 6

Open S32C6 on NCC Online ↗

A curtain required by S32C5 must be—

a fire safety curtain—

made of non-combustible material; and

capable of withstanding a pressure differential of 0.5 kPa over its entire surface area; and

so fitted that when fully lowered it inhibits the penetration of smoke around the perimeter of the opening, from the stage; or

a curtain—

having fire hazard properties complying with Specification 7; and

protected by a deluge system of open sprinklers installed along the full width of the curtain.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S32C6.