Specification clause · NCC 2025 Volume One
S32C6 Proscenium curtains
Specification 32 Construction of proscenium walls · NCC 2019: Spec H1.3: 6
A curtain required by S32C5 must be—
a fire safety curtain—
made of non-combustible material; and
capable of withstanding a pressure differential of 0.5 kPa over its entire surface area; and
so fitted that when fully lowered it inhibits the penetration of smoke around the perimeter of the opening, from the stage; or
a curtain—
having fire hazard properties complying with Specification 7; and
protected by a deluge system of open sprinklers installed along the full width of the curtain.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S32C6.