Specification clause · NCC 2025 Volume One

S43C11 Supply of water for fire-fighting purposes

Specification 43 Bushfire protection for certain Class 9 buildings

Open S43C11 on NCC Online ↗
Varied in NSW. Check the variation for your state.

Water for fire-fighting purposes must be available and consist of—

a fire hydrant system complying with E1D2, or

a static water supply consisting of tanks, swimming pools, dams or the like, or a combination of these, together with suitable pumps, hoses and fittings, capable of providing the required flow rate for a period of not less than 4 hours, determined in consultation with the relevant fire brigade.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S43C11.