S43C2 Separation from classified vegetation
Specification 43 Bushfire protection for certain Class 9 buildings
(1) The building must be separated from classified vegetation—
by not less than the minimum distances specified in Table S43C2; or
such that radiant heat flux on exposed building elements will not exceed 10kW/m².
(2) For the purposes of (1), the term ‘classified vegetation’ has the meaning that it has in AS 3959.
Table S43C2 Minimum distance of building to classified vegetation
Vegetation classification
Slope
Minimum distance (m) of the building to classified vegetation
High risk
Upslope and flat land
60
High risk
Downslope max 20 degrees
110
Medium risk
Upslope and flat land
40
Medium risk
Downslope max 20 degrees
80
Low risk
Upslope and flat land
30
Low risk
Downslope max 20 degrees
50
Table Notes
Table values are based on a Fire Danger Index of 100 in accordance with AS 3959.
High risk equates to vegetation classification of forest and woodland in accordance with AS 3959.
Medium risk equates to vegetation classification of scrub and rainforest in accordance with AS 3959.
Low risk equates to vegetation classification of shrubland, mallee/mulga and grassland in accordance with AS 3959.