Specification clause · NCC 2025 Volume One

S43C2 Separation from classified vegetation

Specification 43 Bushfire protection for certain Class 9 buildings

Open S43C2 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) The building must be separated from classified vegetation—

by not less than the minimum distances specified in Table S43C2; or

such that radiant heat flux on exposed building elements will not exceed 10kW/m².

(2) For the purposes of (1), the term ‘classified vegetation’ has the meaning that it has in AS 3959.

Table S43C2 Minimum distance of building to classified vegetation

Vegetation classification

Slope

Minimum distance (m) of the building to classified vegetation

High risk

Upslope and flat land

60

High risk

Downslope max 20 degrees

110

Medium risk

Upslope and flat land

40

Medium risk

Downslope max 20 degrees

80

Low risk

Upslope and flat land

30

Low risk

Downslope max 20 degrees

50

Table Notes

Table values are based on a Fire Danger Index of 100 in accordance with AS 3959.

High risk equates to vegetation classification of forest and woodland in accordance with AS 3959.

Medium risk equates to vegetation classification of scrub and rainforest in accordance with AS 3959.

Low risk equates to vegetation classification of shrubland, mallee/mulga and grassland in accordance with AS 3959.

Tables

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S43C2.

State and territory variations all clauses side by side →