Specification clause · NCC 2025 Volume One
S43C3 Separation between buildings
Specification 43 Bushfire protection for certain Class 9 buildings
(1) The building must be located not less than 12 m from any other building.
(2) The separation distance required by (1) need not be complied with if the building is constructed—
with external walls that have an FRL of not less than 60/60/60 when tested from the outside, including any openings protected in accordance with AS 3959 for BAL—19 or greater; or
for external walls and roof, using a material or system that satisfies the test criteria of AS 1530.8.1 for a radiant heat flux of 10 kW/m² or greater.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S43C3.