S43C8 Exposed external areas

Specification 43 Bushfire protection for certain Class 9 buildings

Open S43C8 on NCC Online ↗

An external area designed to hold people unable to be safely accommodated within the building, that may be exposed to radiant heat flux from a fire front during a bushfire event, must not be exposed to an incident radiant heat flux from the fire front exceeding 1 kW/m2 above background solar radiant heat flux.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S43C8.