S5C4 Lintels
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.3
(1) A lintel must have the FRL required for the part of the building in which it is situated.
(2) A lintel need not comply with (1) if it does not contribute to the support of a fire door, fire window or fire shutter, and—
it spans an opening in—
a wall of a building containing only one storey; or
a non-load bearing wall of a Class 2 or 3 building; or
it spans an opening in masonry which is not more than 150 mm thick and—
not more than 3 m wide if the masonry is non-load bearing; or
not more than 1.8 m wide if the masonry is load bearing and part of a solid wall or one of the leaves of a cavity wall.
New in NCC 2025. No S5C4 in NCC 2022 Volume One; it may have moved or been renumbered.