Specification clause · NCC 2025 Volume One

S5C3 Fire protection for a support of another part

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.2

Open S5C3 on NCC Online ↗

(1) Where a part of a building required to have an FRL depends upon direct vertical or lateral support from another part to maintain its FRL, that supporting part, subject to (2), must—

have an FRL not less than that required by other provisions of this Specification; and

if located within the same fire compartment as the part it supports have an FRL in respect of structural adequacy the greater of that required —

for the supporting part itself; and

for the part it supports; and

be non-combustible —

if required by other provisions of this Specification; or

if the part it supports is required to be non-combustible.

(2) The following building elements need not comply with (1)(b) and (1)(c)(ii):

An element providing lateral support to an external wall complying with S5C24(1)(b) or C2D12.

An element providing support within a carpark and complying with S5C19, S5C22 or S5C25.

A roof providing lateral support in a building—

of Type A construction if it complies with S5C15(a), (b) or (d); and

of Type B and C construction.

A column providing lateral support to a wall where the column complies with S5C6(1) and (2).

An element providing lateral support to a fire wall or fire-resisting wall, provided the wall is supported on both sides and failure of the element on one side does not affect the fire performance of the wall.

New in NCC 2025. No S5C3 in NCC 2022 Volume One; it may have moved or been renumbered.