S5C3 Fire protection for a support of another part
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 2.2
(1) Where a part of a building required to have an FRL depends upon direct vertical or lateral support from another part to maintain its FRL, that supporting part, subject to (2), must—
have an FRL not less than that required by other provisions of this Specification; and
if located within the same fire compartment as the part it supports have an FRL in respect of structural adequacy the greater of that required —
for the supporting part itself; and
for the part it supports; and
be non-combustible —
if required by other provisions of this Specification; or
if the part it supports is required to be non-combustible.
(2) The following building elements need not comply with (1)(b) and (1)(c)(ii):
An element providing lateral support to an external wall complying with S5C24(1)(b) or C2D12.
An element providing support within a carpark and complying with S5C19, S5C22 or S5C25.
A roof providing lateral support in a building—
of Type A construction if it complies with S5C15(a), (b) or (d); and
of Type B and C construction.
A column providing lateral support to a wall where the column complies with S5C6(1) and (2).
An element providing lateral support to a fire wall or fire-resisting wall, provided the wall is supported on both sides and failure of the element on one side does not affect the fire performance of the wall.
Clauses referred to
- S5C24 Type C fire-resisting construction — fire-resistance of building elements
- C2D12 Performance of external walls in fire
- S5C19 Type A fire-resisting construction — carparks
- S5C22 Type B fire-resisting construction — carparks
- S5C25 Type C fire-resisting construction — carparks
- S5C15 Type A fire-resisting construction — roof: Concession
- S5C6 General concessions