Specification 5 Fire-resisting construction
45 clauses · Open on NCC Online ↗
- S5C1 ScopeThis Specification contains requirements for the fire-resisting construction of building elements.
- S5C2 Exposure to fire-source featuresA part of a building element is exposed to a fire-source feature if any of the horizontal straight lines between that part and the fire-source…
- S5C3 Fire protection for a support of another partWhere a part of a building required to have an FRL depends upon direct vertical or lateral support from another part to maintain its FRL, that…
- S5C4 LintelsA lintel must have the FRL required for the part of the building in which it is situated. (2) A lintel need not comply with (1) if it does not…
- S5C5 Method of attachment not to reduce the fire-resistance of building elementsThe method of attaching or installing a finish, lining, ancillary element or service installation to the building element must not reduce the…
- S5C6 General concessionsSteel columns — A steel column, other than one in a fire wall or common wall, need not have an FRL in a building that contains— only 1 storey; or 2…
- Table S5C7 Increased FRLs — Construction surrounding mezzaninesLevel otherwise required for any FRL criterion (mins) | Increase in level to not less than (mins) 30 | 60 60 | 90 90 | 120 120 | 180 180 | 240 Table…
- S5C7 Mezzanine floors: ConcessionThis Clause does not apply to a Class 9b building that is a spectator stand or audience viewing area accommodating more than 100 persons as…
- S5C8 Enclosure of shaftsShafts required to have an FRL must be enclosed at the top and bottom by construction having an FRL not less than that required for the walls of a…
- S5C9 Carparks and ancillary uses for Class 2 and 3 buildingsA Class 7 part of a building may be regarded as Class 2 for the purpose of determining the relevant fire-resisting requirements of this…
- S5C10 Residential care building: ConcessionIn a Class 3 building protected with a sprinkler system complying with Specification 17 and used as a residential care building, any FRL criterion…
- Table S5C11a Type A construction: FRL of loadbearing parts of external wallsDistance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C11b Type A construction: FRL of non-loadbearing parts of external wallsDistance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C11c Type A construction: FRL of external columns not incorporated in an external wallColumn type | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 Load…
- Table S5C11d Type A construction: FRL of common walls and fire wallsWall type | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 Load…
- Table S5C11e Type A construction: FRL of loadbearing internal wallsLocation | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8…
- Table S5C11f Type A construction: FRL of non-loadbearing internal wallsLocation | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8…
- Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11fBuilding element | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8…
- S5C11 Type A fire-resisting construction — fire-resistance of building elementsIn a building required to be of Type A construction— each building element listed in Tables S5C11a, S5C11b, S5C11c, S5C11d, S5C11e, S5C11f and…
- S5C12 Type A fire-resisting construction — concessions for floorsA floor need not comply with Table S5C11g if— it is laid directly on the ground; or in a Class 2, 3, 5 or 9 building, the space below is not a…
- S5C13 Type A fire-resisting construction — floor loading of Class 5 and 9b buildings: ConcessionIf a floor in a Class 5 or 9b building is designed for a live load not exceeding 3 kPa— the floor next above (including floor beams) may have an FRL…
- S5C14 Type A fire-resisting construction — roof superimposed on concrete slab: ConcessionA roof superimposed on a concrete slab roof need not comply with S5C11 as to fire-resisting construction if— the superimposed roof and any…
- S5C15 Type A fire-resisting construction — roof: ConcessionA roof need not comply with Table S5C11g if its covering is non-combustible and the building— has a sprinkler system (other than a FPAA101D or…
- S5C16 Type A fire-resisting construction — roof lightsIf a roof is required to have an FRL or its covering is required to be non-combustible, roof lights or the like installed in that roof must— have an…
- S5C17 Type A fire-resisting construction — internal columns and walls: ConcessionFor a building with an effective height of not more than 25 m and having a roof without an FRL in accordance with S5C15, in the storey immediately…
- S5C18 Type A fire-resisting construction — open spectator stands and indoor sports stadiums: ConcessionIn an open spectator stand or indoor sports stadium, the following building elements need not have the FRL specified in Tables S5C11a, S5C11b,…
- S5C19 Type A fire-resisting construction — carparksNotwithstanding S5C11, a carpark may comply with this clause if it is— an open-deck carpark which is a separate building; or protected with a…
- S5C20 Type A fire-resisting construction — Class 2 and 3 buildings: ConcessionIn a Class 2 or 3 building with a rise in storeys of not more than 3— notwithstanding C2D10(1) and (2) and C3D7, timber framing may be used for—…
- Table S5C21a Type B construction: FRL of loadbearing parts of external wallsDistance from a fire-source feature | FRL (in minutes) Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C21b Type B construction: FRL of non-loadbearing parts of external wallsDistance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C21c Type B construction: FRL of external columns not incorporated in an external wallDistance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C21d Type B construction: FRL of common walls and fire wallsWall type | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 Load…
- Table S5C21e Type B construction: FRL of loadbearing internal wallsLocation | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8…
- Table S5C21f Type B construction: FRL of non-loadbearing internal wallsLocation | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8…
- Table S5C21g Type B construction: FRL of other building elements not covered by Tables S5C21a to S5C21fBuilding element | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8…
- S5C21 Type B fire-resisting construction — fire-resistance of building elementsIn a building required to be of Type B construction— each building element listed in Tables S5C21a, S5C21b, S5C21c, S5C21d, S5C21e, S5C21f and…
- S5C22 Type B fire-resisting construction — carparksNotwithstanding S5C21, a carpark may comply with this clause if it is— an open-deck carpark which is a separate building; or protected with a…
- S5C23 Type B fire-resisting construction — Class 2 and 3 buildings: ConcessionIn a Class 2 or 3 building with a rise in storeys of not more than 2— notwithstanding C2D10(1) and (2), timber framing may be used for— external…
- Table S5C24a Type C construction: FRL of parts of external wallsDistance from a fire-source feature | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C24b Type C construction: FRL of external columns not incorporated into an external wallDistance from a fire-source feature | FRL (in minutes): structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class…
- Table S5C24c Type C construction: FRL of common walls and fire wallsWall type | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 Load…
- Table S5C24d Type C construction: FRL of internal wallsLocation | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 Bounding…
- Table S5C24e Type C construction: FRL of roofLocation | FRL (in minutes): Structural adequacy / Integrity / Insulation Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 Roofs |…
- S5C24 Type C fire-resisting construction — fire-resistance of building elementsIn a building required to be of Type C construction— a building element listed in Tables S5C24a, S5C24b, S5C24c, S5C24d and S5C24e and any beam or…
- S5C25 Type C fire-resisting construction — carparksNotwithstanding S5C24, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a…