S7C3 Floor linings and floor coverings
Specification 7 Fire hazard properties · NCC 2019: Spec C1.10: 3
A floor lining or floor covering must have—
a critical radiant flux not less than that listed in Table S7C3; and
in a building not protected by a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, a maximum smoke development rate of 750 percent-minutes; and
a group number complying with S7C6(b), for any portion of the floor covering that is continued more than 150 mm up a wall.
Table S7C3 Critical radiant flux (CHF in kW/m2) of floor linings and floor coverings
Class of building
Building not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17
Building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17
Fire-isolated exits and fire control rooms
Class 2, 3, 5, 6, 7, 8 or 9b, excluding Class 3 accommodation for the aged and Class 9b as specified below
2.2 kW/m2
1.2 kW/m2
2.2 kW/m2
Class 3 accommodation for the aged
4.5 kW/m2
2.2 kW/m2
4.5 kW/m2
Class 9a patient care areas
4.5 kW/m2
2.2 kW/m2
4.5 kW/m2
Class 9a areas other than patient care areas
2.2 kW/m2
1.2 kW/m2
4.5 kW/m2
Class 9b auditorium or audience seating area used mainly for indoor swimming or ice skating
1.2 kW/m2
1.2 kW/m2
2.2 kW/m2
Class 9b auditorium or audience seating area used mainly for other sports or multi-purpose functions
2.2 kW/m2
1.2 kW/m2
2.2 kW/m2
Class 9c resident use area
N/A
2.2 kW/m2
4.5 kW/m2
Class 9c areas other than resident use areas
N/A
1.2 kW/m2
4.5 kW/m2