South Australia variation · NCC 2025 Volume One

SA I3D12 Emergency lighting requirements

SA Part I3 Farm buildings and farm sheds · varies I3D12 Emergency lighting requirements

Open on NCC Online ↗

Delete clause I3D12 and insert SA I3D12 as follows:

An emergency lighting system complying with E4D2 must be installed in a farm building except that—

any area primarily used for the storage of hay can be excluded when calculating the floor area of the storey or room of the building for the purpose of determining emergency lighting requirements; and

emergency lighting is not required where automatic back-up power is provided by a fuel driven back up generator or where no artificial lighting is provided in the building; and

an emergency lighting system is not required in a Group C farm building.

New in NCC 2025. No SA I3D12 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause