South Australia variation · NCC 2025 Volume One

SA I3D9 Fire hydrants and water supplies

SA Part I3 Farm buildings and farm sheds · varies I3D9 Fire hydrants and water supplies

Open on NCC Online ↗

Delete clause I3D9 and insert SA I3D9 as follows:

(1) A farm building need not be provided with a fire hydrant system in accordance with E1D2, if it has—

a fire hydrant system installed in accordance with AS 2419.1 except—

in lieu of 4 hour water supply the minimum on-site water supply quantity must be as set out in Table SA I3D9 for the particular building group; and

for Group A and B buildings over 1000 m2 in floor area each tank used must have a capacity of not less than 72,000 litres; and

for single tank systems compliance with clause 4.3.3 is not required; and

compliance with clause 4.3.1 of AS 2419.1 is not required; and

for buildings incorporating non-fire resistant polystyrene sandwich panel construction, the minimum water supply quantities in Table SA I3D9 must be increased by 50%; and

an on-site pumpset is not required if the design performance of section 2.3 of AS 2419.1 is achieved based on use of a fire truck pump with a capacity of 1,900 litres per minute at 1,000 kPa; and

in lieu of the coverage specified in AS 2419.1, external fire hydrants are located so that every part of the perimeter of a building is within 100 m from a hydrant outlet measured along the shortest distance of travel between or around buildings; or

a water supply system comprising single or multiple on-site water storage tanks with connections for use by the fire brigade and complying with the requirements of AS 2419.1 for water supplies and water storage, except—

in lieu of 4 hour water supply the minimum on-site water supply quantity must be as set out in Table SA I3D9 for the particular building group; and

for Group A and B buildings over 1000 m2 in floor area each tank used must have a capacity of not less than 72,000 litres; and

for single tank systems compliance with clause 4.3.3 of AS 2419.1 is not required; and

for buildings incorporating non-fire-resistant polystyrene sandwich panel construction, the minimum water supply quantities in Table SA I3D9 must be increased by 50%; and

an on-site pumpset need not be provided; and

Group A or B buildings water storage tanks must be distributed so every part of the perimeter of a building is not more than 100 m from a tank suction point, measured along the shortest distance of travel between or around buildings; and

for Group C buildings water storage tanks must be distributed so that every part of the perimeter of a building is within a 200 m radius of a tank suction point; and

all pipes, valves and fittings for water storage tanks and connections must comply with section 5 and sections 8.2, 8.3, 8.6 and 8.7 of AS 2419.1 as relevant.

(2) A dam may be regarded as a water storage tank if it complies with the requirements of section 5 of AS 2419.1 and the water level is maintained above the top of the highest fire brigade suction point at all times.

(3) A hardstand area and vehicular approach from the site entrance, suitable for use by the fire brigade must be provided adjacent to each water storage tank provided under (1)(b).

Insert SA table (I3D9) I3D9 as follows:

SA Table I3D9: Minimum quantities for on site water supplies for farm buildings

Building Group

Floor area (m2)

Minimum water supply quantity (L)

Group A

500 to 1,000

36,000

1,001 to 2,000

72,000

2,001 to 5,000

144,000

Group B

500 to 1,000

72,000

1,001 to 2,000

144,000

Group C

5 L/m2 or 36,000 L at each location, whichever is greater.

Table Notes

A single water supply with the minimum water quantity outlined in Table SA I3D9 can serve more than one building.

New in NCC 2025. No SA I3D9 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause