South Australia variation · NCC 2025 Volume One

SA I4D2 Type of construction required

SA Part I4 Bulk grain storage facilities

Open on NCC Online ↗

Delete clause I4D2 and insert SA I4D2 as follows:

The external walls of a bulk grain storage facility need not be of fire-resisting construction in accordance with Table C2D2 if—

the external walls are 3 m or more from an allotment boundary and more than 6 m from any other building on the same allotment, other than a Class 10 building; and

a fire separation space of not less than 2 m is provided between cell type silos; and

the external walls are of—

non-combustible construction; or

Type C construction.

New in NCC 2025. No SA I4D2 in NCC 2022 Volume One; it may have moved or been renumbered.