Delete clause I4D2 and insert VIC I4D2 as follows:

A communication system must—

contain a back-up power supply; and

have a control that enables the call to be cancelled manually at the point of origin only; and

incorporate a device at the point of origin that indicates the system has operated; and

incorporate an indication panel in the manager’s office or staff area that clearly indicates the point of origin of a call; and

for systems not using personal staff communication devices, have an audible tone that has a continuous signal until deactivated at the point of origin; and

be operational at all times; and

have two call points in each ensuite or combined shower/water closet with one call point located in the shower recess and the other on the wall beside the closet pan ahead of the bowl rim; and

have call points (other than those mentioned in (g)) which are located—

within the reach of a resident whilst in bed; and

in all common habitable rooms; and

in all bathrooms, sanitary compartments and shower rooms where the call point must be of waterproof construction and within the reach of any fallen resident.

Applications

VIC I4D2 only applies to Class 3 and Class 9a residential aged care buildings and Class 9c buildings.

Changed since NCC 2022. See NCC 2022 Volume One VIC I4D2, or show what changed.

The Deemed-to-Satisfy Provisions Delete clause I4D2 and insert VIC I4D2 as follows: A communication system must — contain a back-up power supply; and have a control that enables the call to be cancelled manually at the point of this Part apply origin only; and incorporate a device at the point of origin that indicates the system has operated; and incorporate an indication panel in the manager’s office or staff area that clearly indicates the point of origin of a call; and for systems not using personal staff communication devices, have an audible tone that has a continuous signal until deactivated at the point of origin; and be operational at all times; and have two call points in each ensuite or combined shower/water closet with one call point located in the shower recess and the other on the wall beside the closet pan ahead of the bowl rim; and have call points (other than those mentioned in (g)) which are located — within the reach of a resident whilst in bed; and in all common habitable rooms; and in all bathrooms, sanitary compartments and shower rooms where the call point must be of waterproof construction and within the reach of any fallen resident. Applications VIC I4D2 only applies to Class 3 and Class 9a residential aged care buildings and Class 9c buildings.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Other states and territories