VIC I4D2 Electronic communication system
VIC Part I4 Class 3 and 9a residential aged care buildings and Class 9c buildings
Delete clause I4D2 and insert VIC I4D2 as follows:
A communication system must—
contain a back-up power supply; and
have a control that enables the call to be cancelled manually at the point of origin only; and
incorporate a device at the point of origin that indicates the system has operated; and
incorporate an indication panel in the manager’s office or staff area that clearly indicates the point of origin of a call; and
for systems not using personal staff communication devices, have an audible tone that has a continuous signal until deactivated at the point of origin; and
be operational at all times; and
have two call points in each ensuite or combined shower/water closet with one call point located in the shower recess and the other on the wall beside the closet pan ahead of the bowl rim; and
have call points (other than those mentioned in (g)) which are located—
within the reach of a resident whilst in bed; and
in all common habitable rooms; and
in all bathrooms, sanitary compartments and shower rooms where the call point must be of waterproof construction and within the reach of any fallen resident.
Applications
VIC I4D2 only applies to Class 3 and Class 9a residential aged care buildings and Class 9c buildings.
Changed since NCC 2022. See NCC 2022 Volume One VIC I4D2, or show what changed.
The Deemed-to-Satisfy Provisions Delete clause I4D2 and insert VIC I4D2 as follows: A communication system must — contain a back-up power supply; and have a control that enables the call to be cancelled manually at the point of this Part apply origin only; and incorporate a device at the point of origin that indicates the system has operated; and incorporate an indication panel in the manager’s office or staff area that clearly indicates the point of origin of a call; and for systems not using personal staff communication devices, have an audible tone that has a continuous signal until deactivated at the point of origin; and be operational at all times; and have two call points in each ensuite or combined shower/water closet with one call point located in the shower recess and the other on the wall beside the closet pan ahead of the bowl rim; and have call points (other than those mentioned in (g)) which are located — within the reach of a resident whilst in bed; and in all common habitable rooms; and in all bathrooms, sanitary compartments and shower rooms where the call point must be of waterproof construction and within the reach of any fallen resident. Applications VIC I4D2 only applies to Class 3 and Class 9a residential aged care buildings and Class 9c buildings.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Other states and territories
- WA Delete clause I4D2 and insert WA I4D2 as follows: The Deemed-to-Satisfy Provisions of this Part apply to a WA public…
- NSW Delete clause I4D2 and insert NSW I4D2 as follows: If an entertainment venue forms part only of a building, then— the…
- SA Delete clause I4D2 and insert SA I4D2 as follows: The external walls of a bulk grain storage facility need not be of…
- TAS Delete clause I4D2 and insert TAS I4D2 as follows: Performance Requirements TAS I4P1 to TAS I4P13 are satisfied by…